Spun Concrete Pole Design
A spun concrete pole tapers towards the top, and the loads on it act at several heights: the conductors at the tip, cross-arms and equipment lower down. Its reinforcement is therefore not sized at one section. The calculation first finds the longitudinal steel and spiral required at every height of the pole. You then lay out the zones of constant reinforcement the shop will produce, and the calculation checks them. Why the design runs in these two stages is explained on the Spun Concrete Pole Design page. This page walks through the screens.
Creating the calculation
Pick Spun Pole Design in the Calculation Gallery and add it to your project with "Start Calculation". The input panel is on the left, with Select from Catalog at its top. On the right are five tabs: 3D View, Design, Detailed Design, Takeoff and Test Simulation. Analyze and Design sits on the 3D View tab.
| Section | Data you define |
|---|---|
| Geometry | Pole length, foundation depth, base and top diameters, concrete cover |
| Material | Concrete class, steel grade and the material safety factors |
| Loads | A tip load and torsion, or point loads, cross-arms and equipment at any height |
| Design Options | The TEDAŞ product class and the bar and spiral diameters the design may use |

Selecting from the catalogue
Select from Catalog opens the KamBeton SBA catalogue. The list starts with one representative pole for each top diameter; "Show all types" lists every length and nominal load. Picking a pole fills the length, the outer and inner diameters at the base and the top, the foundation depth and the tip load. The catalogue rates the nominal tip load in kilograms, and it is entered as kilonewtons: 400 kg becomes 4 kN. Nothing is calculated until you run Analyze and Design.
The manufacturer publishes the outer diameters and the weight of each pole. The catalogue's inner diameters are derived from those two, so check the wall thickness against the drawing of the pole you order.
Geometry
You enter the pole length and the foundation depth. The buried length is taken as fixed in the soil, so the analysis starts at ground level and no station lies in the buried part. The note under the foundation depth repeats the ground level.
The base and top sections each take an outer and an inner diameter, and the diameters vary linearly between them. The wall thickness at both ends is shown under the cover.
The concrete cover is measured to the outside of the spiral, so the cover to a longitudinal bar is this value plus the spiral diameter. The form starts at 15 mm, the value TS EN 12843 Annex B gives for a hollow section in exposure class XC4 with concrete below C40/50. Change it if your conditions are different.
Material
You select the concrete class and the steel grade. The material safety factors and start at 1.5 and 1.15, and the design strengths and they give are shown below them. These factors apply to the TS 500 design check. The TEDAŞ safety factor and the bending test simulation work with characteristic strengths, without them.
Loads
The Loads section has two modes.
Simple is for the usual case, where the specification gives the pole a single tip load. You enter the horizontal Tip Load, its Angle in plan, a Tip Torsion if there is one, and the Tip Offset, the distance down from the top at which the load acts. The form starts the offset at 0.25 m, where TEDAŞ-MLZ/99-34 clause 2.6 applies the tip force.
Detailed lets you place loads at any height:
| Load | What you enter | How it acts on the pole |
|---|---|---|
| Point load | Height, horizontal force, angle | Shear and bending below its height. The tip load is the first point load |
| Tip torsion | A torsional moment | Constant torsion below the tip load. Cross-arm torsion is added to it separately |
| Cross-arm | Double or single arm, height, arm length, self weight, vertical and horizontal load, angle | A double arm is symmetric: its vertical loads add axial force only. A single arm also bends the pole with its self weight at mid-arm and its vertical load at the tip. In both, the horizontal load is the net imbalance, and it produces torsion equal to the load times the arm length |
| Equipment | Transformer, projector or box platform, height, angle, dimensions and weights | The transformer platform sits off-centre, so the deck and the transformer bend the pole. The pole passes through the centroid of the projector platform, and a box sits on the axis, so these two add axial force only |
Wind and ice loads are not generated. The tip load in a utility's specification usually already includes them; any additional share can be entered as a point load or as a cross-arm's horizontal load.

Design options
Product class (TEDAŞ) selects the safety factor the pole is designed to.
| Choice | Target safety factor |
|---|---|
| Urban LV/MV shared network | 2.00 |
| Long-span overhead line | 2.21 |
| My own safety factor | The value you enter |
| No class — TS500 only | None: the ratio is reported for information |
A selected class turns the safety factor into a design requirement alongside TS 500: the longitudinal steel is raised until the target is reached. New calculations start with the urban class.
Longitudinal Rebar Candidates and Spiral Rebar Candidates are the diameters the design may use. At each station it takes the smallest diameter in the list that is adequate, so the result tends towards many thin bars. If you want thicker bars, take the thin diameters out of the list.
Analyze and Design
Analyze and Design on the 3D View tab runs the first stage. Three things happen:
- The internal forces and the required longitudinal steel and spiral are computed at every station.
- If you have no zones yet, one rebar zone and one stirrup zone covering the whole pole are proposed, sized for the most demanding station.
- Those zones are checked at once, and the 3D view switches to its analytical mode.
In Analytical mode the buttons along the top choose what is drawn on the pole: Loads, Required As, Required Stirrup, or one of the six internal force diagrams N, V2, V3, M22, M33 and T. Physical returns to the pole itself.

Reading the Design tab
The bar at the top of the Design tab gives the verdict: Design Adequate, Design Inadequate or Not verified — Check when the zones have changed since the last check. Beside it are the number of rebar and stirrup zones, the approximate steel weight and how it compares with a single zone. The buttons below it are How to use?, Generate Report and Check.
The TEDAŞ Safety Factor card below gives the factor against its target with a PASS or FAIL badge, the nominal and breaking tip forces, the first section to reach capacity, the lever arm and the characteristic strengths used. With a product class selected the verdict covers both requirements: a pole whose sections all pass but whose factor stays below the target is reported as Design Inadequate, and the bar says by how much.
The two drawings show the zones against what the stations require: Longitudinal Rebar Zones and Design Envelope and Stirrup Zones and Design Envelope. Beside them are the sections at the upper and lower ends of the zone, with the bars, the spiral and the clear spacing between bars. Under the drawings each zone has its card: start and end height, count and diameter for a rebar zone; type (spiral or hoop), diameter, spacing and single or double wrap for a stirrup zone. The badge on each card says whether the zone is adequate, not covered, does not fit geometrically, or is inadequate.
To split a zone, Shift-click its band in the drawing at the height you want, or use Add Rebar Zone, which halves the longest zone. After any change, Check verifies the new layout.

When a code detailing rule fails while the sections still carry the load, the bar shows a separate notice outside capacity badge. These notices do not change the verdict; Details lists them with the station heights they apply to.
Analysis and Design Station Points, closed at the bottom of the tab, is the table behind the envelopes. The stations are spaced at regular intervals along the pole, with one more at every height a load acts on. Each row gives the height, the outer and inner diameter, the six internal forces, the moment capacity, and the longitudinal bars and spiral that station alone would need. The values are a guide for laying out the zones; the verdict comes from the check of the zones themselves.

Optimising the zones
Laying out the rebar zones by hand is not necessary. Optimise Zones computes the lightest layout for every number of zones and shows them together. In the window you choose the bar diameter, the largest number of zones, the shortest zone you accept and the stock bar length the shop cuts from. The chart plots the longitudinal steel against the number of zones for each candidate diameter, and the table lists, for each zone count, the takeoff, the steel actually purchased once the offcuts are counted, the waste and the layout.
The row marked most economical buys the least steel; among rows that buy the same, it is the one with the fewest zones. Select it picks that row, and Apply replaces the rebar zones with it and runs the check again. The weights cover longitudinal steel only; the exact takeoff comes from the Takeoff tab. How the search works is described on the Spun Concrete Pole Design page.
Detailed Design
The Detailed Design tab opens on the two Most Critical Sections: the section that governs the longitudinal steel and the section that governs the transverse steel, usually at different heights. Inspect by Zone has a button for each rebar zone and each stirrup zone, and opens the governing station of that zone; its calculation is fetched when you click it.
The selected section has three tabs. Detailed Calculation lists the steps in groups (longitudinal reinforcement, flexure, shear in each direction, torsion and detailing rules), each with the formula, the numbers substituted into it and the outcome, and the code clause where the step comes from one. Interaction Diagram shows the section's N-M envelope with its demand, and Section State the fiber stresses, which are computed on demand with "Compute fiber state".

Takeoff and the detail drawing
The Takeoff tab produces the exact quantities from the zones you applied. The detailing options follow shop and specification practice:
| Option | Starts at | What it sets |
|---|---|---|
| Fixed lap (ר) | Blank | Blank uses the lap length the TS 500 formula gives |
| Max bar length (mm) | 12000 | The stock length bars are cut from |
| Waste (%) | 0 | Added to every weight |
| Spiral end extra turns | 1.5 | Extra turns at each end of a spiral |
| Max splice at one section (%) | 50 | Above half, the lap lengths are multiplied by 1.5 as TS 500 requires |
Generate Final Takeoff + Drawing gives the total steel with its longitudinal and spiral parts, the concrete volume with the steel per cubic metre, a summary by diameter and the bar schedule. Each mark in the schedule has its diameter, count, unit and total length, the height range it covers and a note such as the end anchorage length. The development and lap lengths used are listed below the schedule.

Below the schedule is the detail drawing, and Download DXF saves it. The preview shows the drawing as it is laid out in model space, where the sections are drawn at full size and therefore look small beside the pole. The DXF also carries an A4 fabrication sheet in paper space: the pole elevation, the stirrup and spiral zones, the developed layout of the longitudinal bars, the rebar schedule, the concrete quantity, the base and top sections and the pole's data table, with the sections brought to a readable size by their viewport.

Test Simulation
The Test Simulation tab predicts what the TS EN 12843 clause 5.5.2 bending test will measure on the reinforcement you applied. Under Test Settings you can enter the concrete and steel strengths you expect from production control; left blank, the catalogue classes are used. These values are used by the simulation only; the design always uses the ordered classes. The Elastic limit / safety factor ratio starts at 0.75: the specification's annex figure marks the elastic limit at 1.65 P for the 2.21 class, and 1.65 / 2.21 is 0.75. Simulate Test runs the analysis, and its result is saved with the calculation.
The Pushover Curve plots the tip force against the lateral displacement. Dashed lines mark the computed events, and solid lines the specification's limits for the elastic limit and for breaking. The table below gives each event (the nominal tip force, cracking onset, first yield and breaking) with its force, its ratio to the nominal force, the lateral displacement, the section where it occurs, the specification limit and the difference from it.

This tab gives no verdict: whether the design is adequate is decided on the Design tab. The breaking force here can differ slightly from the TEDAŞ card's, because the pushover uses a concrete model that carries tension while the design uses the code's stress distribution. Test Observations lets you enter the displacements from a real test report next to the prediction; adding or removing a row does not change the computed events.
Generating the report
Generate Report on the Design tab produces the PDF.
| Section | Contents |
|---|---|
| 1. Summary | The verdict, the highest demand/capacity ratio of each layer with its height, and the TEDAŞ safety factor |
| 2. Geometry | Length, diameters, foundation depth and cover |
| 3. Material and Design Parameters | Material classes and factors |
| 4. Loads | The loads you entered and their reduction to the pole axis |
| 5. Internal Force Diagrams | N, V2, V3, M22, M33 and T along the pole |
| 6. Longitudinal Reinforcement | The rebar zones against the required envelope |
| 7. Transverse Reinforcement | The stirrup zones against the required envelope |
| 8. Capacity Check Summary | The check of every zone |
These are followed by the governing section of each layer with its detailed calculation steps and the analysis station table. When the bending test has been simulated, its pushover is added; when the takeoff has been generated on the Takeoff tab, the takeoff and the detail drawing are added at the end.


The report follows the language of the interface: run a calculation in the English UI and the report comes out in English.
Publishing and verification
Publish at the top of the page opens the Publishing & Verification window. Publish This Version freezes the calculation as it stands, its inputs and results together, into a copy that does not change, and gives that copy a verification link. Anyone with the link sees the copy read-only, without signing in. Editing the calculation afterwards leaves the copy as it was. Publishing a state that is already published returns the same publication instead of a second one.
While the calculation is in its published state, the window marks it Current. Download PDF with QR, and Generate Report too, then produce the report with a QR code that opens the link. Once an input changes, the report no longer matches the publication and the QR is left out. Publish again to get a link for the new state.

The Publications list holds every version with its date and the number of times its link has been opened. Each can be copied, opened or revoked. Revoking is permanent: the link stops working.
Whether the results are current
The state of your result is shown under the input panel.
| State | What it means |
|---|---|
| Analyzed | The saved result is current. The engine version and the time of the run are shown with it |
| Inputs changed | You changed a design input after the analysis, so the results no longer belong to the pole on screen |
| Outdated engine | The result was produced with an earlier version of the calculation engine |
While the results are out of date, the Design and Detailed Design tabs say so and offer Analyze and Design. The test settings and observations are not design inputs, so changing them leaves the design current.
When you want to study the section's behaviour
This macro designs the pole and checks it against TS 500 and the TEDAŞ safety factor. To study one of its sections on its own, its moment-curvature curve or the effect of prestressing strands, you can model it in the Section Analysis macro. Its step-by-step use is on the How to Use Section Analysis page.
Which rules the calculation applies, how the zones and the safety factor are computed and what it leaves out are covered on the Spun Concrete Pole Design page.