StructuralMind

Footfall Analysis — Verification

Updated:

On this page

Footfall Analysis is tested against the worked examples of SCI P354, CCIP-016 and AISC DG11. A worked example is the guide's own numerical example repeated from start to finish; it shows that the method is coded correctly. The response chain is also compared with ETABS's time-history solution of the same floor, and machine vibration is tested against the guides' formulas and independent closed-form solutions. For stairs the calculation is compared with SAP2000's solution of the same stairs.

Results

ExampleReferenceQuantities comparedLargest deviation
SCI P354 D.1, composite office floorWorked example30.03 %
SCI P354 D.2, lightweight residential floorWorked example3−0.15 %
SCI P354 D.3, rhythmic activityWorked example5−0.02 %
CCIP-016 Example 1, footbridgeWorked example530.82 %
CCIP-016 Example 2, post-tensioned floorWorked example340.83 %
CCIP-016 Example 3, ribbed laboratory floorWorked example4equal to the printed precision
AISC DG11 Example 7.1, steel composite floorWorked example91.3 %
AISC DG11 Example 7.2, live concertWorked example30.16 %
AISC DG11 Example 7.3, sensitive equipmentWorked example60.50 %
AISC DG11 Examples 4.1 and 7.1, composite sectionWorked example62.4 %
Office floor, ETABS time-history solutionAnother program's solution712.4 %
Machine vibrationClosed form1310⁻⁶
PartitionsGuide value and model rules510⁻⁹
AISC DG11 Example 4.6, stairWorked example3equal to the printed precision
SCI P354 resonant response on a stairClosed form110⁻¹⁵
Three stairs, SAP2000 comparisonAnother program's solution111.26 %

The deviation is the calculation's value divided by the guide's value, minus 1. The guides print their tables to two or three significant figures, so the deviations given for those tables are the part of the difference beyond the rounding of the printed last digit.

SCI P354

SCI P354 D.1, composite office floor

The guide's example D.1 computes, with Eq 50, the resonant response to walking of a composite office floor with a natural frequency of 9.30 Hz and 4.68 % damping. The modal mass is 10,226.8 kg and the walker weighs 746 N.

QuantityGuide's valueCalculationDeviation
Weighted RMS acceleration aw,rmsa_{w,rms} (m/s²)47.39 × 10⁻³47.404 × 10⁻³+0.03 %
Response factor RR9.489.481+0.01 %
Allowed number of events nan_a2,4052,405.1+0.01 %

The guide rounds the frequency weighting W=8/9.30=0.86022W = 8/9.30 = 0.86022 to 0.86, which is where the 0.03 % comes from.

SCI P354 D.2, lightweight residential floor

The guide's example D.2 computes, with Eq 51, the transient response of a lightweight residential floor with a natural frequency of 13.6 Hz to a single footfall. The modal mass is 1,181.26 kg and the pace is 2.2 Hz.

QuantityGuide's valueCalculationDeviation
Weighted RMS acceleration aw,rmsa_{w,rms} (m/s²)199.95 × 10⁻³199.648 × 10⁻³−0.15 %
Response factor RR39.9939.93−0.15 %
Allowed number of events nan_a3,2393,239.2+0.01 %

The guide rounds the effective impulse 60×2.21.43=185.27560 \times 2.2^{1.43} = 185.275 to 185 (+0.15 %) and the frequency weighting 8/13.6=0.588248/13.6 = 0.58824 to 0.59 (−0.30 %). The two roundings together give the −0.15 %.

SCI P354 D.3, rhythmic activity

The guide's example D.3 computes, with Eq 52–55, the ultimate limit state load of a floor with a natural frequency of 8.1 Hz and 1.6 % damping under normal jumping.

QuantityGuide's valueCalculationDeviation
Governing activity frequency fpf_p (Hz)2.7 (h=3h = 3)2.7 (h=3h = 3)0
Dynamic magnification Dδ,1D_{\delta,1} / Dδ,2D_{\delta,2} / Dδ,3D_{\delta,3}1.12 / 1.80 / 31.251.1249 / 1.7987 / 31.25equal to the printed precision
Equivalent load FF (kN/m²)20.9420.937−0.02 %

The guide's load coefficients (Tables 3.1 and 3.3, Eq 20), effective impulse (Eq 18), frequency weighting curves (Eq 21–23) and walking velocity (Eq 16) are also compared with their printed values one to one.

CCIP-016

CCIP-016 Example 1, footbridge

The guide's Example 1 gives the resonant response of a two-span footbridge at 1.55 Hz and 2.2 Hz pacing rates, mode by mode and harmonic by harmonic (Tables 5.2 and 5.3). Every cell of the two tables is compared.

QuantityGuide's valueCalculationDeviation
Table 5.2, total RR (1.55 Hz)5.655.644−0.10 %
Table 5.3, total RR (2.2 Hz)6.386.347−0.51 %
Tables 5.2 and 5.3, cells50 cellsat most 0.82 %
Hand check, RR at 2.32 Hz (p. 44)8.58.46−0.4 %

The ordinate of the second mode at mid-span is computed from the shape of the fixed-pinned span mode the guide describes in §5.1.1. It comes out at 0.957, and its square (0.917) agrees with the ratio of Table 5.2's mode-2 cells to a unit ordinate (0.916–0.921).

CCIP-016 Example 2, post-tensioned floor

The guide's Example 2 gives the resonant response of a post-tensioned floor bare (2.2 Hz, Table 5.6) and finished (2.35 Hz, Table 5.5). The excitation and response points are different.

QuantityGuide's valueCalculationDeviation
Table 5.6, total RR (bare floor)5.645.648+0.14 %
Table 5.6, cells33 cellsat most 0.83 %
Table 5.5, total RR (finished floor)5.305.266−0.64 %

Table 5.5's cells are consistent with a frequency of about 7.05 Hz rather than with the inputs given in the text (7.0 Hz, 24,100 kg, 3 %), so the finished floor is compared on its total RR. The governing third harmonic is little affected, and the total deviates by 0.64 %.

CCIP-016 Example 3, ribbed laboratory floor

The guide's Example 3 computes the high-frequency (transient) response of a ribbed laboratory floor both with hand-calculated modes and with finite element modes (Tables 5.8 and 5.9).

QuantityGuide's valueCalculation
RMS velocity vrmsv_{rms}, hand modes (mm/s)0.100.104
Peak velocity, hand modes (mm/s)0.400.406
RMS velocity vrmsv_{rms}, finite element modes (mm/s)0.070.0715
Response factor RR1.041.041

The guide's printed values come from the ten of Table 5.8's eleven modes below 2f1=22.22 f_1 = 22.2 Hz. The calculation likewise takes the modes below 2f12 f_1 for the transient response, as §4.3.1 says.

AISC DG11

AISC DG11 Example 7.1, steel composite floor

The guide's Example 7.1 computes the resonant and transient response to walking of a composite office floor on steel beams with the 38 modes of Table 7-2. The result is a peak acceleration as a percentage of gravity (%g).

QuantityGuide's valueCalculationDeviation
Resonant step, 3.49 Hz (%g)0.3740.3753+0.35 %
Resonant step, 4.89 Hz (%g)0.3510.3556+1.3 %
Resonant step, 7.05 Hz (%g)0.1730.1729−0.04 %
Resonant step, 8.85 Hz (%g)0.2420.2423+0.13 %
Dominant frequencies (Hz)12.6 and 8.8512.6 and 8.850
Effective impulse of mode 22, IeffI_{eff} (lb·s)1.011.012equal to the printed precision
Peak acceleration of mode 22 (%g)0.2060.2059−0.05 %
Equivalent sinusoidal peak acceleration, ESPA (%g)0.3140.3153+0.40 %
Total peak acceleration of the 38 modes (%g)0.8650.857−0.94 %

The resonant steps are computed with the guide's printed frequency response function (FRF) values. The 4.89 Hz step comes out at 0.3556 %g from the printed inputs, and the 1.3 % is not explained by their rounding; the other three steps are within 0.35 %. The FRF built from the mode ordinates of Table 7-2 is about 11 % below the curve of Figure 7-10 at both peaks.

With the guide's 0.005 s sampling step of Eq 7-6, the ESPA is 0.3140 %g. The −0.94 % in the total peak acceleration comes from the mode ordinates being printed to three significant figures.

AISC DG11 Example 7.2, live concert

The guide's Example 7.2 computes the response of an 18.7 psf crowd at a 3 Hz live concert harmonic by harmonic and combines the harmonics with the 1.5-power rule of Eq 7-10.

QuantityGuide's valueCalculationDeviation
First harmonic ap,1a_{p,1} (%g)1.111.113+0.24 %
Second harmonic ap,2a_{p,2} (%g)1.881.879−0.03 %
Combined peak acceleration (%g)2.412.414+0.16 %

AISC DG11 Example 7.3, sensitive equipment

The guide's Example 7.3 computes the one-third octave band velocity at a sensitive instrument on a floor walked on at a fast pace, and compares it with the generic criteria of Table 6-2.

QuantityGuide's valueCalculationDeviation
Dominant frequency (Hz) and step frequency (Hz)10.9 and 2.1810.9 and 2.180
Effective impulse of mode 19, IeffI_{eff} (lb·s)1.321.320+0.03 %
Peak acceleration of mode 19 (%g)0.08430.08425−0.06 %
Total peak acceleration (%g)0.1560.1568+0.48 %
Calibrated peak acceleration (%g)0.2340.2351+0.48 %
One-third octave band velocity V1/3V_{1/3} (mips)2,8502,864+0.50 %

The intermediate values agree with the guide's printed three significant figures. The 0.50 % in the band velocity lies within the rounding of the printed mode table.

AISC DG11 Examples 4.1 and 7.1, composite section

The composite section values of steel beams acting with the slab are compared with those of the guide's Examples 4.1 and 7.1. The slab of Example 7.1 is 5¼ in. of lightweight concrete on a 2 in. deck.

QuantityGuide's valueCalculationDeviation
Slab moment of inertia across the ribs (in⁴/ft)34.334.33+0.08 %
Slab moment of inertia along the ribs (in⁴/ft)102101.6−0.43 %
W16x26 interior beam, composite moment of inertia (in⁴)1,1001,126+2.4 %
W16x26 edge beam, composite moment of inertia (in⁴)1,0101,027+1.7 %
W24x55 girder, 24 ft span (in⁴)3,9704,061+2.3 %
W24x55 girder, 16 ft span (in⁴)3,6703,727+1.5 %

Example 7.1 shows no working for its section values and refers to Example 4.1; the same calculation gives Example 4.1's beam within 0.5 %. Moments of inertia 1.5–2.4 % above Example 7.1's make the floor slightly stiffer and its natural frequency slightly higher.

VC criteria

The vibration criteria for sensitive equipment (VC curves) are taken from each guide's own table.

GuideCriterionVC-AVC-BVC-CVC-DVC-E
SCI P354 Table 5.6RR on the WgW_g base curve0.50.250.1250.06250.0313
CCIP-016 Table 3.2RR on its base curve0.50.250.1250.06250.03125
AISC DG11 Table 6-2One-third octave band velocity (mips)2,0001,000500250125

In a calculation under AISC DG11, an area with a VC class or an operating theatre (4,000 mips) is read as a velocity, and the pace of the person walking past it is taken from Table 6-1.

Office floor, ETABS time-history solution

For this comparison an office floor with flat-plate and 12 m beam bays, walls and openings is built in ETABS with its own objects. A 1 kN vertical sine force, standing for one walking harmonic, acts at the floor's governing point for RR, and ETABS's modal time-history solution is taken at 35 frequencies from 4 to 18 Hz.

QuantityMeasured
Steady-state sum with ETABS's modes / ETABS time history, at the peaks (8.69 / 16.29 / 17.52 Hz)at most 0.11 %
Same ratio, whole sweepat most 2.8 % (below the first modes)
8.7 Hz peak with MindFEM's modes / ETABSamplitude +3.6 %, frequency −2.1 %
16.3 Hz and 17.5 Hz peaks with MindFEM's modes / ETABS+12.4 % and −11.5 %
Static deflection under 1 kN at the same point / ETABS+5.8 %
SCI P354 RR (walking at 2.2 Hz), with MindFEM's modes / with ETABS's modes7.44 / 7.30 (+1.95 %)
SCI P354 Eq 36 / ETABS time history, at the peaks1.148 / 1.230 / 1.141

The first two rows show that MindFEM's steady-state calculation, given ETABS's modes, reproduces ETABS's time-history solution. The other differences between MindFEM and ETABS come from the two programs' modelling — the shell formulation, the mesh and the way mass is distributed. The two close modes at 16.3 and 17.5 Hz have the same shape in both programs (MAC 0.97 and 0.92), but different amplitudes at this free-edge point.

Within one harmonic, SCI P354 Eq 36 adds the modal contributions with their signs and without their phases. The time-history solution, which the guide names the most accurate method in §6.4.1 (Eq 31), carries each mode's phase against the force. At resonance the resonant mode lags the force by a quarter period while modes far from it move in phase or in antiphase, so their peaks do not occur at the same instant, and Eq 36 gives 14–23 % more at the peaks. Under self excitation, where the walker and the receiver are the same point, every modal contribution is positive, so Eq 36 is never below the time-history solution and the result is on the safe side. Under full excitation, with the walker and the receiver apart, that order does not hold. The calculation applies Eq 36 as the guide recommends.

Machine vibration

The force a rotating machine applies to the floor and the floor's steady-state response are tested against the guides' formulas and independent closed-form solutions.

What was testedReferenceResult
Force from the balance grade, F=m G Ω/1000F = m\,G\,\Omega/1000ISO 21940-11 Eq 6The same by two routes from the permissible residual unbalance
Force from eccentricity, F=m e ω2SfF = m\,e\,\omega^2 S_f, Sf≥2S_f \geq 2ACI 351.3R Eq 3-3Equal; Sf<2S_f < 2 refused
Steady-state acceleration of one modeClosed formEqual
Two machines in one one-third octave band, combined by SRSSClosed formEqual
One-third octave band limitsAISC DG11 Table 7-5Equal
Natural frequencies within 20 % of the running frequencyACI 351.3R §3.4.3Equal
Speed range sweep, force with the square of the speedACI 351.3R §3.2.2.1Peak of a mode inside the range equal to the closed form to 10⁻⁹
Rigid-base transmissibility crossing 1 at r=2r = \sqrt{2} for every dampingACI 351.3R Fig. 3.14Equal
Undamped transmissibility 1/8 at r=3r = 3 (about 90 % isolation)SCI P354 B.3.2Equal
Isolator frequency from static deflection, 3.15 Hz for 25 mmf=g/δ/2πf = \sqrt{g/\delta}/2\piEqual
Mass-spring model on a very stiff floorRigid-base transmissibility10⁻⁶
Mass-spring model on a one-mode floorDirect solution of the two-degree-of-freedom system10⁻¹⁰
Support classISO 20816-3 §5.3Equal

The guides do not include a worked example that solves a floor together with a machine on it, so this section rests on the formulas and closed-form solutions. Two successive solves of the same model can differ in RR by up to 0.12 %; the finite element mesh is not built bit for bit the same each time, and the difference shows for a machine running right next to a mode.

Partitions

When the stiffness of partitions is counted, the spring value of AISC DG11 §7.2 and the rules of the model are tested.

What was testedBasisResult
The sum of the springs along a wall, 2.0 kip/in./ft (1,149 kN/m per metre) × the length meeting the slabAISC DG11 §7.2Equal, 10⁻⁹
No spring over an opening that reaches the edge meeting the slabModel ruleEqual
The shells of a masonry wall massless, its top free, the fundamental frequency risingModel ruleHolds
A slab node at each edge of a door opening, and wall over the openingModel ruleHolds
Two crossing walls sharing one node at every height along their intersectionModel ruleHolds

A comparison with a floor measured with its partitions is not part of this page.

Stairs

AISC DG11 Example 4.6, stair

AISC DG11 Example 4.6 computes, by the hand method (Eq 4-8), the peak acceleration of three descents on a steel stair spanning 36.9 ft, weighing 15.5 kips, with a fundamental frequency of 7.02 Hz and 3 % damping. The calculation solves the same stair with the finite element method's equation (Eq 7-8) and the first mode of a simply supported beam.

DescentGuide valueCalculatedDeviation
Normal descent1.44 %g1.440 %g0.02 %
Rapid descent2.08 %g2.076 %g−0.20 %
Rapidly descending group6.23 %g6.228 %g−0.04 %

On a single-mode stair Eq 7-8 equals Eq 4-8, so the deviations come from the guide printing three significant figures.

SCI P354 resonant response on a stair

On a single-mode stair with a 6 Hz fundamental frequency, 5 t modal mass and 2 % damping, the second harmonic of Table 3.2 is resonant at a 3 Hz pace. The response factor computed by hand from the two harmonics' WbW_b-weighted responses is R=116.14R = 116.14; the calculation gives the same value within 10⁻¹⁵ and the governing pace frequency of 3 Hz.

Three stairs, SAP2000 comparison

The modes and response of a steel U stair, a concrete U stair and a spiral stair drawn on the floor plan are compared with SAP2000. The fundamental frequencies agree within 1.26 %, the SCI P354 response factor within 0.87 % and the AISC DG11 peak accelerations within 0.18 %. The models, the comparison tables and the SAP2000 model files are on the Stair vibration, comparison with SAP2000 page.

Model files

The ETABS model that produced the office floor comparison can be downloaded. It opens in ETABS 20 and later with File > Import > ETABS .e2k File.

What this calculation covers

TopicStatus
Vibration of a measured floorThe comparisons on this page are against the guides' examples and another program's solution. There is no comparison with a measured floor.
SCI P354's stair methodApplied with the coefficients of Table 3.2 and full resonant build-up, which is on the safe side.
AISC DG11's stair methodThe method of §7.4.3 is for slender stairs.
SCI P354's finite element examples (D.1.7, D.2.6) and the measured floors of Appendix ATheir model inputs (sections, masses, supports) are not in the guide, so they are not rebuilt.
SCI P354 load coefficients outside 1.8–2.2 HzTable 3.1 gives values for this range; outside it the coefficients are extended with the table's formula.
WbW_b or WgW_g weighting in offices and dwellingsSCI P354 Table 5.1 and the guide's base curves differ. The weighting curve is the room type's preset and can be changed by hand.
AISC DG11 §7.5, between fLf_L and fUf_UThe guide names neither the resonant nor the impulse method there. The calculation blends the two linearly in frequency across that range.
Sensitive equipment under machineryThe velocity in the one-third octave band of the machine's frequency is compared with the VC curve. The guides calibrate the VC curves for walking.
Several machines swept over speed rangesEach machine's worst speed is combined by SRSS as if they coincided, which is on the safe side.
Mass-spring modelVertical only. The machine is one mass at one node, the isolators one spring, and rocking is not included.
Machine start-up and run-downOnly the running speeds are swept. On start-up a machine passes briefly through its isolators' resonance; ISO 10137 §5.2.1 asks that this be considered and gives no numerical criterion.
ISO 20816-3 zone valuesOnly the support class is given. The standard's zone values are for vibration measured on the machine's own bearings and are not compared with the floor's vibration.

Sources

  • SCI P354, Design of Floors for Vibration (2009)
  • CCIP-016, A Design Guide for Footfall Induced Vibration of Structures (2006)
  • AISC Design Guide 11, 2nd edition (2016)
  • ACI 351.3R-04, Foundations for Dynamic Equipment
  • ISO 21940-11:2016
  • ISO 20816-3:2022
  • BS 6472:1992