The vertical earthquake effect: which members TBDY 2018 asks to analyse separately

TBDY 2018 accounts for the vertical earthquake effect in most buildings with an approximate value proportional to the dead load. For long-span beams, cantilevers, columns supported on beams and inclined columns it asks for a separate analysis based on the local vertical vibration modes of those members.

Mustafa Tümer Tan · Founder

Share
A glass-clad building cantilevering far out on both sides above its lower storey
On this page

The natural period of a building in the vertical direction is much shorter than its horizontal period. The vertical design spectrum of TBDY 2018 also reaches its peak at shorter periods than the horizontal one. Columns are very stiff axially, so for the building as a whole the vertical acceleration stays a small addition to the dead load. The vertical mode of a long-span beam or a long cantilever, however, can fall on the highest part of that spectrum. The question that decides the vertical earthquake analysis is whether the building has such a member.

This post summarises the rules that the Turkish Building Earthquake Code (TBDY 2018) sets for the vertical earthquake effect.

Vertical elastic design spectrum

Under TBDY 2.3.5, the vertical elastic design spectral acceleration SaeD(T)S_{aeD}(T) is defined from the short-period design spectral acceleration coefficient SDSS_{DS} of the horizontal spectrum (Equation 2.5):

SaeD(T)={(0.32+0.48 TTAD)SDS0≤T≤TAD0.8 SDSTAD≤T≤TBD0.8 SDS TBDTTBD≤T≤TLDS_{aeD}(T) = \begin{cases} \left(0.32 + 0.48\,\dfrac{T}{T_{AD}}\right) S_{DS} & 0 \le T \le T_{AD} \\[6pt] 0.8\,S_{DS} & T_{AD} \le T \le T_{BD} \\[6pt] 0.8\,S_{DS}\,\dfrac{T_{BD}}{T} & T_{BD} \le T \le T_{LD} \end{cases}

The corner periods of the vertical spectrum are obtained from those of the horizontal spectrum (Equation 2.6):

TAD=TA3,TBD=TB3,TLD=TL2T_{AD} = \frac{T_A}{3}, \qquad T_{BD} = \frac{T_B}{3}, \qquad T_{LD} = \frac{T_L}{2}

The plateau of the vertical spectrum is at 0.8 SDS0.8\,S_{DS} and ends at one third of the period where the horizontal plateau ends. Short-period vertical modes fall on this plateau.

Members that need a separate analysis

TBDY 4.4.3.1 requires a separate vertical earthquake analysis in buildings of Earthquake Design Class DTS = 1, 1a, 2 and 2a for the following members:

  • (a) Beams whose spans have a horizontal projection of 20 m or more.
  • (b) Cantilevers whose spans have a horizontal projection of 5 m or more.
  • (c) Columns supported on beams.
  • (d) Columns inclined to the vertical.

The analysis is based on the local vertical vibration modes of these members and is carried out for these members only. It uses the vertical spectrum of 2.3.5 and the Modal Response Spectrum Method of 4.8.2. In this analysis R/I=1R/I = 1 and D=1D = 1 are used for all structural systems, so the vertical earthquake effect is not reduced.

A column supported on a beam is a type B3 irregularity in TBDY. If the column sits on a beam supported at both ends, 3.6.2.4(b) states that the vertical earthquake analysis of 4.4.3 is sufficient. A column may never be placed on the tip or the top of a cantilever beam (3.6.2.4(a)).

Part 1 of Eurocode 8 (EN 1998-1, 4.3.3.5.2) gives a similar list. If the design vertical ground acceleration exceeds 0.25g0.25g, the vertical component is taken into account for:

  • horizontal members spanning 20 m or more,
  • cantilevers longer than 5 m,
  • horizontal prestressed members,
  • beams supporting columns,
  • base-isolated structures.

TBDY limits the analysis to these members only. EN 1998-1 adds the elements that directly support them (4.3.3.5.2(3)).

Approximate value for the other members

For the parts of the structural system outside the members of 4.4.3.1, and for buildings that do not fall under that definition, the vertical earthquake effect is found without a special analysis from Equation 4.10:

Ed(Z)≈23 SDS GE_d^{(Z)} \approx \frac{2}{3}\,S_{DS}\,G

Here Ed(Z)E_d^{(Z)} is the vertical earthquake effect and GG is the dead load effect. The two analyses are not alternatives to each other. The code itself decides which member is designed with which analysis.

The approximate value scales the dead load effect by a factor proportional to SDSS_{DS}. It does not account for the vertical vibration mode of the member or for the distribution of its mass along the span. That is why the code asks for a modal analysis for the members whose vertical mode can govern.

Vertical mass in the model

In the horizontal earthquake analysis, floors are usually modelled as rigid diaphragms. The storey mass is lumped at the centre of mass and assigned to the two horizontal translations and the rotation about the vertical axis. In that model there is no vertical mass along the span of a beam or cantilever, so its local vertical mode never appears.

For the vertical analysis the mass has to be distributed to the nodes along the member. The mass that the floor delivers to the beam is distributed in the same way. TBDY gives no separate modelling rule for this analysis. EN 1998-1 4.3.3.5.2(2) allows a partial model that contains the members on which the vertical component acts. A partial model accounts for the stiffness of the adjacent members.

Load combinations and the sign

In the Modal Response Spectrum Method the modal contributions are, as a general rule, combined with the Complete Quadratic Combination rule (Annex 4B.2.4). The combined result has no sign. Whether the vertical earthquake acts with gravity or against it is therefore defined separately in the load combination. The two combinations of TBDY 4.4.4.1 are:

G+Q+0.2S+Ed(H)+0.3 Ed(Z)(4.11)G + Q + 0.2S + E_d^{(H)} + 0.3\,E_d^{(Z)} \qquad (4.11) 0.9G+H+Ed(H)−0.3 Ed(Z)(4.12)0.9G + H + E_d^{(H)} - 0.3\,E_d^{(Z)} \qquad (4.12)

Here QQ is the live load, SS the snow load and HH the lateral earth pressure effect. Ed(H)E_d^{(H)} is the horizontal earthquake effect after the directional combination and carries both signs itself (Equation 4.9). The vertical effect enters the combination at 30%. The first combination represents the case where the vertical earthquake adds to gravity and the second the case where it reduces it. Tension in a column or uplift at a support appears in the second combination.

In steel buildings designed with Load and Resistance Factor Design, 1.2G1.2G is used in place of GG in Equation 4.11 (4.4.4.2).

Conclusion

The vertical earthquake effect does not carry the same weight in every building. In a stiff building with short spans, the approximate value proportional to the dead load is sufficient. Long-span beams, long cantilevers, columns supported on beams and inclined columns are the members for which TBDY asks for a separate analysis. For these members the accuracy of the analysis depends on modelling the vertical mass along the member and on setting up both signs of the load combination.

Mustafa Tümer Tan

About the author

Mustafa Tümer Tan

Civil engineer (M.Sc.) and founder of StructuralMind.

Get new posts by email

Engineering writing and product notes, straight to your inbox.

Unsubscribe at any time.Privacy Policy

Share

Start calculating in minutes.

Sign up, pick a calculation, and produce your first auditable report.