In conventional seismic design a building dissipates earthquake energy by damage to its own members. Plastic hinges at beam ends and at the base of walls are part of that design. In seismic isolation, most of the displacement demand is taken in a single plane, the isolation interface. Above that plane the superstructure stays almost elastic.

This post summarises the rules that Chapter 14 of the Turkish Building Earthquake Code (TBDY 2018) sets for the design of isolated buildings. Chapter 14 covers new isolated buildings and existing buildings retrofitted with isolation.

How isolation changes the building's response

Under TBDY 14.2.1, the purpose of seismic isolation is to reduce the earthquake forces acting on the structural system. To do so, the natural period of the building is lengthened, its energy dissipation capacity is increased, or both. A building with a longer period has a lower spectral acceleration. The hysteretic behaviour of the isolators adds damping to the system.

A longer period means a large displacement at the isolation interface. The code therefore also requires the isolation system to bring the building back towards its original position (14.3.7):

  • The difference between the force at the maximum displacement under the DD-1 ground motion and the force at half of that displacement must be at least 0.025W0.025W, where WW is the weight of the building.
  • The period calculated with the secondary stiffness must not exceed 6 seconds.

The building importance factor of an isolated building is taken as I=1I = 1 (14.3.2). The importance of the building is reflected in the choice of performance objective instead.

Performance objectives

The design uses two ground motion levels (14.3.3): DD-2 is the design earthquake ground motion and DD-1 is the maximum earthquake ground motion. Each part of an isolated building is designed for one of them (Table 3.5):

PartGround motion levelPerformance objective
Superstructure, DTS = 1, 2, 3, 3a, 4, 4aDD-2Limited Damage (SH)
Superstructure, DTS = 1a, 2aDD-2Immediate Occupancy (KK)
Isolation system and substructureDD-1Immediate Occupancy (KK)

The table is for new buildings. For existing buildings retrofitted with isolation, the superstructure objective is one level lower: Controlled Damage (KH) in place of Limited Damage, and Limited Damage (SH) in place of Immediate Occupancy.

The response modification factor RR and the overstrength factor DD used in the superstructure design are given in Table 14.1:

Performance objectiveRRDD
Immediate Occupancy (KK)1.21.2
Limited Damage (SH)1.51.5

A high-ductility reinforced concrete frame is designed with R=8R = 8 (Table 4.1). With RR at most 1.5, the superstructure of an isolated building is designed to stay almost elastic. The substructure and superstructure may be designed to the limited ductility level (14.3.4).

Isolators

Chapter 14 covers two types of isolator (14.1.2):

  • Elastomeric isolators are built from alternating layers of rubber and steel plates (14A.1). The rubber layers provide the horizontal flexibility. The steel plates keep the bearing stiff under vertical load. In low- and high-damping bearings the damping depends on the rubber compound. In lead-rubber bearings most of the energy is dissipated by the yielding lead core. The characteristic strength of the bearing is the area of the lead core times its shear yield stress (14A.4).
  • Curved surface sliders consist of a slider and one or more concave steel surfaces (14B.1). The radius of curvature sets the period and the friction coefficient provides the damping. The period of a single-surface slider does not depend on the weight it carries: T=2πRe/gT = 2\pi\sqrt{R_{\text{e}}/g}, where ReR_{\text{e}} is the radius of curvature of the surface and gg is the acceleration of gravity.

Matters not covered in Chapter 14 follow TS EN 1337-1 and TS EN 15129 (14.3.12). Isolators must carry the CE mark (14.8.1).

Lower and upper bound properties

The stiffness and damping of an isolator vary with manufacturing tolerances, temperature, ageing, velocity and axial load (14.4.3, 14.11.2). The code therefore asks for two separate analyses (14.3.6):

  • The maximum displacement of the isolation system is calculated at DD-1 with the lower bound properties. A softer system moves further.
  • The maximum lateral force on the superstructure is calculated at DD-2 with the upper bound properties. A stiffer system passes more force to the superstructure.

The bound values are set by 14.12.1 for elastomeric isolators and by 14.13.1 for curved surface sliders. Floor accelerations and equipment checks may use the nominal values (14.3.10).

Choosing the analysis method

An isolated building does not always have to be analysed in the time domain. TBDY 14.14.1 defines three methods.

The Equivalent Lateral Load Method may be used when all of the following conditions are met:

  • (a) The soil is of type ZA, ZB, ZC or ZD.
  • (b) The effective period under DD-1 is shorter than 4.0 seconds.
  • (c) There are at most 4 storeys and at most 20 m of height above the isolation interface.
  • (d) No uplift or tension occurs in the isolators.
  • (e) The effective damping ratio is below 30%.
  • (f) The torsional irregularity coefficient is below 2.0 on every storey and the building has no B2 type irregularity.
  • (g) The vertical period is at most 0.1 seconds.

The Modal Response Spectrum Method needs only conditions (a), (b) and (d).

Nonlinear time history analysis may be used in every case. When the soil is ZE or ZF, the effective period is 4 seconds or longer, or tension occurs in the isolators, it is the only method allowed. It is sufficient to model only the isolators as nonlinear. The substructure and superstructure may remain linear elastic (14.3.8).

Time history analysis

The record selection and scaling rules of TBDY 2.5 also apply to isolated buildings. Chapter 14 adds its own rules:

  • The analysis is run with at least eleven record pairs for each ground motion level and each direction. No more than three records may come from the same earthquake (2.5.1.3, 14.14.4.4).
  • In a three-dimensional analysis, the records are scaled so that the mean of the resultant spectra, each the square root of the sum of the squares of the two horizontal components, is at least 1.3 times the design spectrum (2.5.2.1).
  • The scaling range runs from 0.5 TM0.5\,T_M to 1.25 TM1.25\,T_M (14.14.4.2), where TMT_M is the effective period at the maximum displacement. The TMT_M at the lower end of the range is calculated with the upper bound properties, and the TMT_M at the upper end with the lower bound properties.
  • When the vertical period exceeds 0.1 seconds, the vertical component is included as well (14.14.4.1).
  • The design value is the mean of the maximum values obtained from the analysis with each record (14.14.4.4). The isolator displacement is the vector resultant of the two orthogonal displacements at each time step (14.14.4.5).
  • The results have a lower limit. Isolation interface displacements may not be less than 80% of the value from the Equivalent Lateral Load Method. In buildings without irregularities the 80% limit applies to the substructure and superstructure forces (14.14.4.6, 14.14.4.7).
  • When the soil is weaker than ZD, a three-dimensional dynamic soil–structure interaction analysis is carried out (14.14.4.3).

Tension, stability and clearance

As a rule, no tension may occur in the isolators at any ground motion level (14.4.4). Where tension must be resisted, special isolators whose behaviour in tension has been verified by testing may be used.

The stability of the isolation system is demonstrated by an analysis at DD-1 with the lower bound properties (14.5.1). The safety factor of the isolation system against overturning is at least 1.0 (14.5.3). If uplift or tension occurs in any isolator, the analysis must also show that the building remains stable.

An unobstructed clearance equal to the calculated maximum displacement is left around the isolation system (14.3.11). Once the isolators are installed, this clearance and the services crossing the interface are checked on site (14.7.1). The isolators must remain accessible for the life of the building, with enough room to replace them if needed (14.7.2).

Conclusion

In seismic isolation the focus of the design moves from the ductility of the superstructure to the isolation interface. The superstructure stays almost elastic, while the isolation system and substructure must meet the Immediate Occupancy objective even under the maximum earthquake ground motion. Choosing the isolator alone does not meet that objective. The uncertainty in the isolator properties is covered by the lower and upper bound analyses, and the ground motion by a sufficient number of correctly scaled records.

Mustafa Tümer Tan

About the author

Mustafa Tümer Tan

Civil engineer (M.Sc.) and founder of StructuralMind.

Get new posts by email

Engineering writing and product notes, straight to your inbox.

Unsubscribe at any time.Privacy Policy

Share

Start calculating in minutes.

Sign up, pick a calculation, and produce your first auditable report.