Lateral sway under vertical load: gravity sway
When the structure or its vertical loading is asymmetric, a building sways under vertical load alone. This post covers why the sway occurs, why some analysis methods show it and others do not, and what it means for the design.
Mustafa Tümer Tan · Founder

On this page
An engineer who sees a building sway in a model with no earthquake or wind load defined usually looks for an error in the model. When the structure or its vertical loading is asymmetric, the sway is not a modelling error. Lateral sway under vertical load (gravity sway) is a real behaviour that comes from the geometry and load distribution of the structure, and a three-dimensional analysis shows it.
Why does the sway occur?
In a structure with symmetric geometry and symmetric loading, vertical load causes no lateral displacement. Real structures are rarely fully symmetric. The following three situations cause lateral sway under vertical load:
- Eccentrically loaded walls and cores. When slabs bear on a core from one side only, the core carries an eccentric axial load. The loaded side of the section shortens more than the other side, the core bends, and the storey sways.
- Asymmetric geometry and differential axial shortening. In frames with unequal spans or cantilevers, the beam end moments do not balance at the joints, and the columns take up the difference by bending. A wall and a column standing side by side under different stresses also shorten by different amounts, which creates end moments in the beams. Because the system is not symmetric, these moments can only be balanced by a lateral sway of the storey.
- Inclined columns. An inclined column turns part of the vertical load into a horizontal force. In a column at an angle to the vertical that carries a vertical load , the horizontal component of the axial force is . This force is carried through the floor diaphragm to the lateral load resisting system, and because it acts permanently it causes a permanent sway.
What each analysis method shows
Whether the sway under vertical load appears depends on the analysis method.
Floor-by-floor load transfer (chase-down). Each floor slab is solved on its own and its support reactions are passed to the floor below as loads. Because lateral equilibrium between floors is not solved, the sway under vertical load does not appear. Columns and walls behave as if they carried axial load only.
Three-dimensional building analysis. All elements of the structure are solved together in a single stiffness matrix. If the structure or its loading is asymmetric, the sway under vertical load and the moments that come with it appear in the results.
A three-dimensional analysis loaded in a single step applies the vertical load to the whole finished building at once. During construction, each floor is built plumb and level. The sway of the lower floors is not carried into upper floors that have not yet been built. The magnitude of the sway in the finished building therefore depends on the construction sequence and on the creep of the concrete. The sway from a single-step analysis is not that magnitude. The sway from a single-step analysis shows in which direction and on which floors the structure tends to sway.
What it means for the design
Second-order effects. The second-order indicator in TBDY 2018 4.9.2 is calculated from the reduced storey drifts in the earthquake direction. If its largest value exceeds , the internal forces are increased by the second-order amplification factor. Here is the response modification factor, the overstrength factor, and a coefficient taken as 0.5 for reinforced concrete buildings and 1.0 for buildings with steel or composite columns. This indicator does not include the sway under vertical load. A P-Delta analysis with geometric stiffness built from the vertical load combination does include it.
How it differs from an initial imperfection. Eurocode 2 (5.2) represents the out-of-plumb that comes from construction tolerances by an initial inclination, with a basic value of 1/200. The sway under vertical load does not replace this imperfection. The initial inclination is an assumption about tolerances, while the sway under vertical load is a displacement calculated from the stiffness and load distribution of the structure itself.
Member forces. The sway under vertical load can change the moment diagrams of beams and the axial forces and moments of columns and walls. In most buildings the change does not govern the design. In very tall buildings and in structures with marked asymmetry it can.
Plumbness during construction. As the building rises, the sway grows. For work that needs to be plumb, such as the facade and the lift shafts, the direction of the sway should be known at the design stage and measured and compensated during construction.
Conclusion
A vertical load analysis should be used not only to size columns and walls but also to check the lateral equilibrium of the structure. Sway under vertical load in a three-dimensional analysis is not an error. It shows the direction in which the structure tends to sway and feeds into the second-order analysis, the beam design and the construction planning.
In MindFEM, the P-Delta effect is calculated with geometric stiffness built from the vertical load combination. A comparison of this calculation with ETABS on a four-storey steel frame is given on the verification page.