Seismic assessment of existing buildings: Eurocode 8-3 and ASCE 41 compared

In the assessment of an existing building the uncertainty lies not only in the earthquake but in the building itself. This post compares Eurocode 8-3 and ASCE 41 on knowledge levels, limit states, hazard levels and analysis methods, and brings in TBDY 2018 on knowledge levels.

Mustafa Tümer Tan · Founder

Share
Debris of a reinforced concrete building that collapsed in an earthquake, with a broken beam
On this page

In a new building, material strengths and reinforcement details are written in the drawings. In an existing building they are obtained by survey and testing, and they are never complete. Assessment codes turn this uncertainty into a factor. The more the building has been inspected and tested, the less its capacity is reduced.

This post compares two documents written for the seismic assessment of existing buildings. They are the European standard EN 1998-3:2005 (Eurocode 8-3) and the American standard ASCE/SEI 41. Where stated, ASCE 41 values refer to the ASCE 41-13 edition. TBDY 2018 Chapter 15 is added to the comparison where relevant.

Knowledge level and factor

All three documents divide the scope of the information gathered from the building into levels and give each level a factor:

Eurocode 8-3ASCE 41-13TBDY 2018
Knowledge levelsKL1 (limited), KL2 (normal), KL3 (full)Minimum, Usual, ComprehensiveLimited, Comprehensive
FactorConfidence factor CF = 1.35, 1.20, 1.00Knowledge factor κ\kappa = 0.75 or 1.0 (0.90 under conditions)Knowledge level factor 0.75, 1.00
Applied toMean material properties are divided by CFExpected capacity is multiplied by κ\kappaMember capacity is multiplied by the factor

Eurocode 8-3. The CF values are recommended values, and each country may change them in its National Annex (Table 3.1). In the capacity calculation, the mean material properties obtained from in-situ tests are divided by CF (3.5(1)P). When calculating the force that a ductile component delivers to a brittle one, the mean properties are multiplied by CF instead (3.5(2)P). The knowledge level also limits the choice of method. At KL1 only the Lateral Force and Modal Response Spectrum methods may be used. At KL2 and KL3 all methods may be used.

ASCE 41-13. κ\kappa is generally taken as 0.75 or 1.0 depending on the scope of the data collected and multiplies the component capacity. The value 0.90 may be used only under specific conditions. At the minimum knowledge level κ=0.75\kappa = 0.75. If the material strengths are given in the design documents, the target is Life Safety or a lower performance level, and a linear procedure is used, κ=0.90\kappa = 0.90 may be taken.

TBDY 2018. Chapter 15 defines two knowledge levels. The factor is 0.75 for the limited knowledge level and 1.00 for the comprehensive level, and it applies to member capacities (Table 15.1). Unless stated otherwise, material strengths are not divided by material factors (15.2.12).

At the lowest knowledge level 1/1.35≈0.741/1.35 \approx 0.74, so all three documents apply a reduction of about one quarter. Eurocode 8-3 applies it to the material properties, while ASCE 41 and TBDY apply it to the member capacity. How much a lower material strength reduces a member capacity depends on how strongly that capacity depends on the strength.

Limit states and performance levels

Eurocode 8-3 defines damage through three limit states (2.1(1)P):

  • Damage Limitation (DL): The structure is only lightly damaged. Structural elements do not yield significantly and retain their strength and stiffness. Permanent drifts are negligible and no repair is needed.
  • Significant Damage (SD): The structure is significantly damaged but retains some lateral strength and stiffness. Vertical elements still carry the vertical loads. Moderate permanent drifts are present. The structure can sustain after-shocks of moderate intensity, but it is likely to be uneconomic to repair.
  • Near Collapse (NC): The structure is heavily damaged. Its residual lateral strength and stiffness are low, while the vertical elements still carry the vertical loads. Large permanent drifts are present. The structure would probably not survive another earthquake, even of moderate intensity.

The structural performance levels of ASCE 41 are Immediate Occupancy (IO), Life Safety (LS) and Collapse Prevention (CP). The definitions in the two documents are not identical, but their order is similar. They can be compared with DL against IO, SD against LS and NC against CP.

The collapse definition of Eurocode 8-3 is closer to actual collapse than the one in EN 1998-1, which is written for new buildings. The "no collapse" requirement of EN 1998-1 corresponds roughly to the SD limit state (2.1(1)P, Note).

Hazard levels

Eurocode 8-3 recommends the following return periods for the protection considered appropriate for ordinary new buildings (2.1(3)P, Note):

Limit stateProbability of exceedance in 50 yearsReturn period
Damage Limitation (DL)20%225 years
Significant Damage (SD)10%475 years
Near Collapse (NC)2%2,475 years

Each country decides in its National Annex which limit states are checked and which return periods apply (2.1(2)P, 2.1(3)P).

ASCE 41-13 defines two hazard levels for existing buildings. BSE-1E is the earthquake with a 20% probability of exceedance in 50 years (225 years). BSE-2E is the earthquake with a 5% probability of exceedance in 50 years (975 years). The suffix "E" marks them as reduced hazard levels for existing buildings, below those used for new buildings. The Basic Performance Objective for Existing Buildings (BPOE) for Risk Categories I and II is Life Safety at BSE-1E and Collapse Prevention at BSE-2E. Tier 1 and Tier 2 evaluations are carried out at BSE-1E only, and the Tier 3 evaluation at both levels.

The two documents differ here. The return periods recommended by Eurocode 8-3 correspond to the protection considered appropriate for ordinary new buildings. ASCE 41 assesses existing buildings at a lower hazard level than new buildings.

Analysis methods and checks

Eurocode 8-3 defines five methods (4.4.1). They are lateral force analysis, modal response spectrum analysis, nonlinear static (pushover) analysis, nonlinear time history analysis and the behaviour factor (q) approach. Every method except the q-factor approach uses the unreduced elastic spectrum (2.2.1(2)P). Ductile elements are checked in terms of deformation and brittle elements in terms of strength (2.2.1(3)P).

The Lateral Force Method has an additional condition in Eurocode 8-3. Over the ductile primary elements, the ratio between the largest and smallest demand-to-capacity ratios must not exceed a limit between 2 and 3 (4.4.2). The recommended limit is 2.5. With this condition, linear analysis is limited to buildings where the inelastic demand is spread fairly evenly over the elements.

The pushover analysis uses at least two lateral load distributions (4.4.4.2). One is a uniform distribution proportional to mass and the other a modal distribution. The target displacement is defined by EN 1998-1 4.3.3.4.2.6 and may be determined with the informative Annex B of EN 1998-1 (4.4.4.4). The method of Annex B is known as the N2 method. In buildings where higher modes matter, their contribution is taken into account separately (4.4.4.5).

In ASCE 41 every component action is either deformation-controlled or force-controlled. In the linear procedures, the acceptance criterion for deformation-controlled actions is m κ QCE≥QUDm\,\kappa\,Q_{CE} \ge Q_{UD}. Here QUDQ_{UD} is the demand from earthquake and gravity loads, QCEQ_{CE} the expected capacity calculated with mean material properties, and mm a factor representing the ductility of the component. For force-controlled actions, the demand may be taken as the largest force that the components delivering it can develop with their expected strengths. In the nonlinear static procedure the target displacement is δt=C0 C1 C2 Sd\delta_t = C_0\,C_1\,C_2\,S_d. Here SdS_d is the spectral displacement at the effective period. C0C_0 converts the displacement of the single-degree-of-freedom system to the roof displacement of the building. C1C_1 and C2C_2 represent the amplification of displacement by inelastic behaviour.

Conclusion

Eurocode 8-3 and ASCE 41 answer the same question: how much damage an existing building will suffer in a given earthquake. They differ in how they turn uncertainty into a number through the knowledge level and in how they choose the hazard level. Eurocode 8-3 reduces the material properties and recommends the same return periods as for new buildings. ASCE 41 reduces the capacity and uses reduced hazard levels specific to existing buildings. Besides the code, the outcome of an assessment depends on how far the building has been inspected and tested.

Mustafa Tümer Tan